Emerson 1C31224G01 Ovation Ethernet Communication Module

Product Brief Introduction
The 1C31224G01 is an Ethernet communication interface module for the Emerson Ovation distributed control system. It provides high-speed Ethernet connectivity between the Ovation controller and upper-level monitoring systems, SCADA platforms and networked devices.
Tag:
Technical Specifications
Ethernet interface: 2×10/100Mbps RJ45 ports, redundant. Communication protocols: TCP/IP, UDP, Ovation Net, Modbus TCP/IP. Maximum data rate: 100Mbps per port. Isolation voltage: 1500V AC Ethernet-to-bus. Backplane current: 500mA @ 5V DC. Power dissipation: 2.5W maximum. Operating temperature range: 0°C to +60°C. Storage temperature range: -40°C to +85°C.
Functional Features
Dual redundant Ethernet ports support network redundancy for high availability. It supports multiple standard industrial communication protocols. Built-in network diagnostics and status indicators enable quick fault identification. It supports automatic link recovery and fault switchover. Hot-swap capability enables online replacement.
Application Scenarios
It is used for DCS to SCADA system communication, plant-wide data integration, remote monitoring connections, third-party system integration, and redundant control network applications in power generation, process and manufacturing industries.
Performance Parameters
Communication rate: 10/100Mbps auto-negotiation. Redundancy switchover time: <100ms. Throughput: 10,000 packets per second. Operating temperature range: 0°C to +60°C. Vibration resistance: 2G @ 10Hz to 500Hz. Shock resistance: 30G.
Material Composition
Front panel is flame-retardant engineering plastic. Circuit board uses FR-4 glass epoxy substrate with Ethernet controllers and magnetic isolation components. RJ45 connectors are shielded metal with gold-plated contacts.
Structural Characteristics
It adopts standard Ovation module form factor with front panel link status LEDs, two RJ45 Ethernet ports, rear backplane connector, and card guide design for rack installation.
Working Principle
It acts as a gateway between the Ovation backplane bus and the Ethernet network, converting system data into Ethernet packets and vice versa. It manages network communication, protocol conversion and data exchange, and supports redundant network operation to ensure continuous communication.
Installation Requirements
Install in any available Ovation chassis slot. Use Category 5e or higher shielded twisted pair Ethernet cables. Configure IP address and network parameters via engineering software. Ensure both ports are connected for redundant operation. Implement reliable system grounding.




    Customers reviews

    There are no reviews yet.

    Be the first to review “Emerson 1C31224G01 Ovation Ethernet Communication Module”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8613639522374
    to whats
    +8613639522374
    to whats
    +8613639522374
    email: anikaqx@gmail.com