Technical Specifications Communication Port: Multiple isolated serial communication channels Supported Protocols: Modbus RTU, Tricon dedicated peer‑to‑peer protocol Backplane Bus: Tricon TriBus redundant backplane bus Isolation Voltage: 1500 V between communication ports and system logic circuit Baud Rate Range: 300‑115200 bps configurable Operating Temperature: 0 °C to +60 °C Storage Temperature: -40 °C to +85 °C Certifications: SIL3, UL, CE, ATEX Module Form: Single‑slot plug‑in Tricon rack module Weight: 1.2 kg
Functional Features Triple‑modular redundant communication processing architecture. Hardware electrical isolation for each external serial communication port. Support hot‑swap online module replacement without interrupting system operation. Complete self‑diagnosis for communication channel, internal circuit and bus status. Front‑panel LED indicators for module running status, fault and port activity. Configurable communication parameters via TriStation configuration software. Real‑time uploading of SIS system variables and fault diagnostic information to external host system.
Application Scenarios Data interaction between Tricon SIS and distributed control system DCS. Connection with safety system human‑machine interface HMI. Modbus RTU communication with plant SCADA monitoring platform. Peer‑to‑peer data exchange between multiple Tricon safety controllers. Oil‑gas and petrochemical plant safety‑system remote monitoring interface. Power‑generation safety‑interlock‑system external data publishing.
Performance Parameters Communication Determinism: Deterministic data refresh synchronized with system scan cycle Redundancy Switching: Seamless communication switching among redundant modules without data loss Diagnostic Coverage: Detect communication link failure, frame error and internal hardware fault Maximum Connection Quantity: Support multiple external host devices access through protocol configuration
Material Composition Circuit substrate: Conformal‑coated industrial printed circuit board. Module frame: Reinforced metal alloy rack insertion frame. Connector parts: Isolated serial port connectors and gold‑plated backplane golden finger. Internal components: Industrial communication processor, isolation optocouplers, ESD protection devices. Fasteners: Anti‑vibration metal locking screws.
Structural Characteristics Single‑slot plug‑in structure matching Tricon standard rack chassis. Front‑panel equipped with serial communication physical ports and status LED indicators. Backplane golden finger interface connecting TriBus redundant backplane bus. Internal integrated electromagnetic shielding structure. Mechanical locking buckle for firm fixing inside rack slot.
Working Principle Module obtains safety system real‑time variable data and diagnostic information from main processor through TriBus backplane bus. Redundant communication processor packs data according to configured industrial protocol. Isolation circuit completes electrical isolation between internal logic and external communication links. Serial physical ports transmit data to external devices and receive external host read‑write requests. Internal diagnostic circuit monitors communication frame error rate, link status and hardware health, and reports fault status to Tricon main controller once abnormality is detected.
Installation Requirements Insert communication module into designated communication slot of Tricon rack chassis. Implement chassis protective grounding complying with official system grounding specification. External communication wiring shall adopt shielded twisted‑pair cables. Separate communication signal cables and high‑power power cables routing. Set communication baud rate, address and protocol parameters via TriStation software before putting into service. Hot‑swap replacement shall strictly comply with site safety operation procedure. Cabinet ambient temperature and humidity stay within rated operating range without condensation.














There are no reviews yet.