Triconex 3721 Digital Output Module

Product Brief Introduction
The 3721 is a 16-channel digital output module for the Triconex Tricon safety instrumented system. It provides galvanically isolated discrete output signals to field devices with triple modular redundancy (TMR) architecture, delivering fault-tolerant control output for safety-critical industrial applications.
Tag:
Technical Specifications
Number of outputs: 16 channels, triple redundant. Output type: Form A normally open relay. Contact rating: 2A @ 250V AC / 30V DC. Isolation: 2500V AC channel-to-system. Power supply: 5V DC from backplane. Power dissipation: 12W. Operating temperature range: 0°C to +60°C. Safety integrity level: SIL 3.
Functional Features
Triple modular redundant architecture provides fault-tolerant operation. Each channel is independently isolated. Built-in self-test and fault detection per channel. Hot-swap capability allows online replacement. Output status indicators per channel. Voted output logic ensures correct output even with one faulty channel.
Application Scenarios
It provides safety-critical discrete control in emergency shutdown systems, fire and gas systems, turbine protection, compressor control, process shutdown systems and SIL-rated safety instrumented functions.
Performance Parameters
Contact rating: 2A resistive. Switching time: <15ms. Safety level: IEC 61508 SIL 3. Mean time between failures: >100,000 hours. Operating temperature range: 0°C to +60°C. Vibration resistance: 2G @ 10Hz to 500Hz.
Material Composition
Front panel: flame-retardant engineering plastic. PCB: FR-4 with conformal coating. Relay contacts: silver alloy. Connectors: gold-plated copper alloy. Housing: metal shielded.
Structural Characteristics
It features standard Triconex card form factor, front panel channel status LEDs, fault indicators, rear backplane connector, card guide rails and ejection lever.
Working Principle
Three independent output sub-circuits each receive command data from the three Tricon control processors. Voter circuits compare the three command sets and drive the output relays only when at least two channels agree, providing fault tolerance and ensuring safe output states even in the event of a single circuit fault.
Installation Requirements
Install in any available I/O slot of Triconex chassis. Ensure module is fully seated and secured. Wire output circuits per contact rating. Install surge suppression for inductive loads. Verify chassis grounding.




    Customers reviews

    There are no reviews yet.