Technical Specifications Number of Channels: 8 isolated analog output channels Signal Output Range: 4‑20 mA DC Conversion Resolution: 12‑bit Full‑scale Accuracy: Less than 0.25% of full‑scale range within 0‑60 °C Output Load Resistance: Maximum 600 Ω per channel Field‑to‑logic Isolation: 1500 V isolation Backplane Interface: Tricon TriBus proprietary bus Operating Temperature: 0 °C to 60 °C Storage Temperature: -40 °C to 85 °C Certifications: SIL3, ATEX, UL, FM Weight: 2.5 kg Dimension: Standard full‑height single‑slot Tricon rack module
Functional Features TMR triple redundant internal analog circuit with hardware output voting. Full‑channel self‑diagnosis for loop open‑circuit, short‑circuit and internal circuit abnormality. Support hot‑swap online module replacement without system shutdown. Front‑panel LED status indicators for pass, fault and each channel activity status. Complete electrical isolation between field instrument side and control system backplane. Output signal calibration configurable through TriStation software. Continuous real‑time monitoring of actual output loop current value.
Application Scenarios Modulating valve control for petrochemical safety interlock loops. Burner management fuel flow regulating control. Refinery flare header pressure adjustment. Steam and gas turbine actuator position control. Safety‑related closed‑loop modulating control in process plant. Power generation unit safety auxiliary regulating loops.
Performance Parameters Voting Mechanism: Two‑out‑of‑three analog signal voting Update Rate: Deterministic analog output update synchronized with system scan cycle Diagnostic Coverage: High safety‑failure diagnostic coverage Load Adaptation: Stable output within 0‑600 Ω field load resistance Temperature Drift: Strictly controlled full‑scale drift under rated operating temperature range
Material Composition Main substrate: Industrial‑grade conformal coated printed circuit board. Mechanical frame: Reinforced alloy rack mounting frame. Connector assemblies: Gold‑plated backplane connectors and termination interface connectors. Internal components: Precision digital‑to‑analog conversion chips, isolation optocouplers, precision reference resistors. Structural fasteners: Vibration‑resistant metal fasteners.
Structural Characteristics Single‑slot plug‑in design matching Tricon standard rack chassis. Front‑panel visual LED indicator group. Field signal wiring completed via external termination panel. Backplane golden finger for TriBus bus connection. Built‑in shielding structure to suppress industrial electromagnetic interference. Locking mechanism to fix module firmly in rack slot.
Working Principle Digital set‑point commands are delivered from main processor via TriBus backplane bus. Three independent redundant circuit branches receive identical digital values and perform digital‑to‑analog conversion separately. Hardware voting circuit compares three analog outputs and produces final voted 4‑20 mA output to field actuators. On‑board measurement circuit samples actual loop current continuously. Diagnostic logic compares measured value with theoretical set‑point, generates fault alarm when deviation exceeds threshold and uploads fault information to host controller.
Installation Requirements Install module in designated slot inside Tricon standard rack. Chassis protective grounding must strictly comply with official system grounding requirements. Field instrument wiring uses shielded twisted‑pair cables, separate analog signal cables from high‑power power cables. Confirm field actuator load resistance falls within module permissible range before power‑on. Hot‑swap replacement must strictly follow site safety operation specifications. Cabinet ambient temperature and humidity must stay within rated scope without condensation. Termination panel wiring screw torque conforms to manufacturer recommended value.














There are no reviews yet.