Technical Specifications Channels:16 Signal Type:4‑20mA, 0‑10VDC configurable Resolution:16‑bit Isolation Voltage:1500V RMS Backplane Power Consumption:280mA @5VDC Operating Temperature:0℃~+60℃ Storage Temperature:-40℃~+85℃ Relative Humidity:5%-95%, non‑condensing Certifications:CE, UL, cUL
Functional Features High‑density 16‑channel analog acquisition, configurable input range, open‑circuit fault detection, group LED status, digital data transmission to RX3i CPU.
Application Scenarios Large‑scale process plant, mass transmitter signal acquisition, water‑treatment multi‑parameter monitoring, RX3i system analog input expansion.
Performance Parameters Measurement accuracy ±0.15% full scale Single‑channel fault does not affect other channels Designed for long‑term continuous process‑control operation Shock & vibration:Comply with IEC 60068
Structural Characteristics Standard RX3i plug‑in rack module Front‑panel grouped LED status indicators Two groups of front‑mount analog signal terminal blocks Backplane gold‑finger bus