GE IC200PWR102 VersaMax 120/240 VAC Expanded Power Supply Module

Product Introduction
The IC200PWR102 is an expanded AC input power supply module for VersaMax PLC systems. It operates with 120/240 VAC input and provides regulated 5 VDC and 3.3 VDC outputs, supporting VersaMax CPUs, NIUs, and I/O modules with enhanced 3.3 VDC capacity.
Tag:
Technical Specifications
I Output voltages are 5 VDC and 3.3 VDC. Maximum output current is 1.5 A total, limited to 1.0 A on the 3.3 VDC channel. Holdup time is 20 ms. Protection includes short-circuit and overload safeguards. Dimensions are 49 mm x 133.4 mm x 39 mm. Weight is 0.26 lbs.
Functional Features
Jumper-selectable input voltage eliminates the need for separate 120 V and 240 V models. Expanded 3.3 VDC output addresses higher backplane current requirements of modern modules. 20 ms holdup time ensures continuity during brief power interruptions. Built-in protection circuits enhance system reliability.
Application Scenarios
Manufacturing automation, process control, material handling, and distributed I/O systems requiring AC-powered backplane supplies with dual DC outputs.
Performance Parameters
1.5 A total output capacity with balanced 5 V and 3.3 V support. 20 ms holdup time exceeds typical power transient durations. 27 VA input rating provides efficient power conversion.
Material Composition
Industrial-grade housing with AC input filtering, rectification, and dual-output DC regulation circuitry.
Structural Characteristics
Compact slim-line design for minimal rack space usage. Jumper block accessible for voltage configuration. Standard VersaMax backplane power connectors.
Working Principle
The module rectifies AC input voltage and converts it to regulated 5 VDC and 3.3 VDC through internal switching power supply circuits. A jumper configures the input voltage range for 120 VAC or 240 VAC operation.
Installation Requirements
Configure jumper for 120 VAC (installed) or 240 VAC (removed) before applying power. Mount on VersaMax CPU carrier, NIU, or power supply booster carrier. Connect AC power to designated input terminals.
Usage Precautions
Incorrect jumper setting at 240 VAC causes module damage or safety hazards. Do not exceed 1.0 A on the 3.3 VDC output or 1.5 A total combined output. Ensure proper grounding of the AC input and carrier. Allow adequate ventilation for heat dissipation.




    Customers reviews

    There are no reviews yet.

    Be the first to review “GE IC200PWR102 VersaMax 120/240 VAC Expanded Power Supply Module”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8613639522374
    to whats
    +8613639522374
    to whats
    +8613639522374
    email: anikaqx@gmail.com