GE IC200MDL742 VersaMax 16-Point 24 VDC Positive Logic Discrete Output Module with ESCP

Product Introduction
The IC200MDL742 is a 24 VDC discrete output module featuring 16 positive logic sourcing outputs with electronic short-circuit protection. It delivers reliable control for industrial automation with built-in protection mechanisms.
Tag:
Technical Specifications
Output channels are 16 discrete sourcing outputs. Output voltage is 18-30 VDC with 24 VDC nominal. Maximum output current is 0.5 A per point and 4 A per group. Groups are 2 isolated groups of 8 points each. Group-to-group isolation is 250 VAC continuous and 1500 VAC for one minute.External power supply is 18-30 VDC. Backplane current is 150 mA typical at 5V. Dimensions are 110 mm x 66.8 mm x 50 mm.
Functional Features
Electronic short-circuit and overcurrent protection improve system reliability. Free-wheeling diodes safeguard against inductive load transients. Two isolated groups provide flexible wiring. LED indicators for each output simplify diagnostics. Built-in protection generates fault signals for overload conditions.
Application Scenarios
Factory automation, material handling, packaging systems, process control, relay and solenoid driving, and applications requiring protected outputs.
Performance Parameters
Less than 0.5 ms response time ensures precise output switching. 0.5 A per point with 4 A per group supports substantial loads. Electronic protection latches until cleared by command or power cycle.
Material Composition
Industrial housing with protected output circuitry and isolation barriers between groups.
Structural Characteristics
Two isolated groups of eight outputs. LED indicators for each point plus OK and FLD PWR LEDs. Compact single-slot design.
Working Principle
Output data from the CPU controls solid-state switches. Protection circuits monitor current per point, latching off outputs that exceed current limits. Free-wheeling diodes clamp inductive kickback.
Installation Requirements
Mount on VersaMax carrier. Connect external 24 VDC supply. Group wiring must respect isolation boundaries between the two output groups.
Usage Precautions
Fault conditions latch and remain until cleared. Verify load current does not exceed 0.5 A per point. Use proper suppression for highly inductive loads. Check amber fault LEDs for overload indication.




    Customers reviews

    There are no reviews yet.

    Be the first to review “GE IC200MDL742 VersaMax 16-Point 24 VDC Positive Logic Discrete Output Module with ESCP”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8613639522374
    to whats
    +8613639522374
    to whats
    +8613639522374
    email: anikaqx@gmail.com