GE IC200MDL740 VersaMax 16-Point 12/24 VDC Positive Logic Discrete Output Module

Product Introduction
The IC200MDL740 is a discrete output module providing 16 sourcing outputs for VersaMax systems. It switches DC loads to the positive side of the supply, delivering reliable control for industrial actuators and devices.
Tag:
Technical Specifications
Number of outputs is 16 sourcing outputs in one group. Output voltage range is 10.2-30 VDC. Nominal voltage is 12/24 VDC. Output current is 0.5 A per point maximum. Inrush current is 2.0 A maximum for 100 ms. On response time is 0.2 ms maximum. Off response time is 1.0 ms maximum. Output voltage drop is 0.3 V maximum. Backplane current consumption is 45 mA at 5V. External power supply is 10.2-30 VDC. Dimensions are approximately 110 x 66.8 x 50 mm.
Functional Features
Positive logic sourcing outputs supply current to loads. One LED per point shows individual on/off state. FLD PWR LED indicates field power presence. OK LED indicates backplane power presence. Hot insertion capability allows replacement without system shutdown. Configurable filter time provides noise immunity.
Application Scenarios
Solenoid valve control, relay driving, indicator lamp switching, DC actuator control, and general-purpose 12/24 VDC output applications.
Performance Parameters
0.2 ms on response time enables high-speed switching. 0.5 A per point drives standard industrial loads. 45 mA backplane current is efficient for 16-point output module.
Material Composition
Industrial housing with solid-state output drivers and LED indicator array.
Structural Characteristics
Single group of 16 outputs simplifies wiring. Compact module supports hot insertion. Compatible with IC200CHS series carriers.
Working Principle
The module receives 16 bits of output data from the CPU. Solid-state switches connect the external DC supply to output terminals when commanded, sourcing current to connected loads.
Installation Requirements
Mount on VersaMax carrier. Connect external 10.2-30 VDC power supply for load switching. Use external suppression circuits for inductive loads.
Usage Precautions
12 VDC output functionality requires module version B or higher. External suppression is mandatory for inductive loads. Do not exceed 0.5 A continuous per point. Use recommended 2 A shorting bar for bused commons.




    Customers reviews

    There are no reviews yet.

    Be the first to review “GE IC200MDL740 VersaMax 16-Point 12/24 VDC Positive Logic Discrete Output Module”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8613639522374
    to whats
    +8613639522374
    to whats
    +8613639522374
    email: anikaqx@gmail.com