Yokogawa AAI141 CENTUM CS Analog Input Module

Product Brief Introduction The AAI141 is a high-density analog input module for the Yokogawa CENTUM CS distributed control system. It acquires 4-20mA current signals from field proce
Tag:

Technical Specifications

Number of input channels: 16. Input signal type: 4-20mA DC current. Resolution: 16-bit. System accuracy: ±0.1% of full scale. Isolation: 500V AC channel-to-bus. Backplane current draw: 350mA @ 5V DC. Power dissipation: 1.8W maximum. Operating temperature range: 0°C to +60°C. Storage temperature range: -40°C to +85°C.

Functional Features

Sixteen-channel high-density current input maximizes I/O per slot. Built-in signal conditioning and digital filtering suppress electrical noise. Open-circuit detection function per channel. Hot-swap capability enables module replacement without system shutdown. Per-channel status indicators provide real-time operating status.

Application Scenarios

It acquires process variable signals from field transmitters for DCS systems in power generation, petrochemical refining, chemical processing and heavy manufacturing industries.

Performance Parameters

Input update rate: 100ms per channel. Common mode rejection ratio: 120dB @ 60Hz. Temperature drift: ±25ppm/°C. Operating temperature range: 0°C to +60°C. Vibration resistance: 2G @ 10Hz to 500Hz. Shock resistance: 30G, 11ms half sine.

Material Composition

Housing: UL 94 V-0 flame-retardant PBT plastic. Circuit board: FR-4 glass epoxy substrate. Connectors: gold-plated copper alloy.

Structural Characteristics

It adopts standard CENTUM card form factor with front panel status LEDs, rear backplane connector, and card guide rails for chassis mounting.

Working Principle

It receives 4-20mA current signals from field transmitters, converts them to precision voltage signals, conditions and digitizes the signals via high-resolution ADC, and transmits the measurement data to the CENTUM controller via the system backplane.

Installation Requirements

Install in any available I/O slot of a CENTUM CS chassis. Ensure the module is fully seated in the card guide and backplane connector. Use shielded twisted pair cables for field wiring, grounded at the system side only. Configure channel parameters via CENTUM engineering workstation.




    Customers reviews

    There are no reviews yet.

    Be the first to review “Yokogawa AAI141 CENTUM CS Analog Input Module”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8613639522374
    to whats
    +8613639522374
    to whats
    +8613639522374
    email: anikaqx@gmail.com