Technical Specifications
Input channels: 8. Input types: 4-20mA, ±10V DC. Resolution: 14-bit. Accuracy: ±0.2% full scale. Isolation: 500V AC. Backplane interface: MicroNet bus. Power dissipation: 3W. Operating temperature range: -40°C to +70°C.
Functional Features
Eight high-accuracy analog inputs. Per-channel range configuration. Signal conditioning and filtering. Channel-to-channel isolation. Hot-swap capability. Status indicators.
Application Scenarios
It expands analog measurement capability for MicroNet engine control, turbine control and process control systems.
Performance Parameters
Update rate: 100ms per channel. Accuracy: ±0.2% full scale. CMRR: 100dB. Operating temperature range: -40°C to +70°C.
Material Composition
Housing: flame-retardant plastic. PCB: FR-4 with conformal coating. Components: precision amplifiers and ADCs. Connectors: gold-plated copper.
Structural Characteristics
MicroNet standard module form factor, front panel status LEDs, rear backplane connector, DIN rail mounting.
Working Principle
It receives analog signals from field instruments, conditions and digitizes them, and transmits measurement data to the main controller over the MicroNet system bus.
Installation Requirements
Mount on MicroNet DIN rail base. Connect to system bus. Wire field instruments. Configure ranges via software.