GE 8206-TI-IS Mark V Isolated Thermocouple Input Module

Product Brief Introduction The 8206-TI-IS is an isolated thermocouple input module for the GE Mark V control system. It interfaces with standard thermocouple types to provide accurate temperature measurement with built-in cold junction compensation for turbine and process temperature monitoring.
Tag:

Technical Specifications

Number of channels: 8. Thermocouple types: J, K, T, E selectable per channel. Measurement range: -270°C to +1820°C depending on type. Resolution: 0.1°C. Accuracy: ±0.5°C typical. Cold junction compensation: ±0.2°C accuracy. Isolation: 500V AC channel-to-bus. Backplane current: 400mA @ 5V DC. Power dissipation: 2W. Operating temperature range: 0°C to +60°C.

Functional Features

Supports all standard thermocouple types. Automatic cold junction compensation eliminates external compensation junctions. Open circuit detection per channel. Channel-to-channel isolation. Hot-swap capability.

Application Scenarios

It measures turbine exhaust temperature, process heating, furnace temperature and bearing temperature in power generation, petrochemical and metal processing industries.

Performance Parameters

Update rate: 200ms per channel. CMRR: 120dB @ 60Hz. Temperature drift: ±0.01°C/°C. Operating temperature range: 0°C to +60°C.

Material Composition

Housing: flame-retardant plastic. PCB: FR-4. Input circuits: precision amplifiers and cold junction sensors. Connectors: gold-plated copper.

Structural Characteristics

Standard Mark V card form factor, front panel status LEDs, rear connector, card guide mounting.

Working Principle

It receives millivolt signals from thermocouples, amplifies and compensates for cold junction temperature, converts values to digital temperature data via ADC, and transmits data to the controller.

Installation Requirements

Install in Mark V chassis slot. Use thermocouple extension wire of matching type. Observe correct polarity. Ground shields at system side.

Usage Notes

Configure thermocouple type per channel. Calibrate periodically. Avoid temperature gradients at terminals. Follow ESD procedures.




    Customers reviews

    There are no reviews yet.

    Be the first to review “GE 8206-TI-IS Mark V Isolated Thermocouple Input Module”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +8613639522374
    to whats
    +8613639522374
    to whats
    +8613639522374
    email: anikaqx@gmail.com