Output
5 VDC: 18 A continuous
+12 VDC: 2 A continuous
−12 VDC: 1 A continuous
Total Power: 90 W maximum
5 VDC: 18 A continuous
+12 VDC: 2 A continuous
−12 VDC: 1 A continuous
Total Power: 90 W maximum
Protection & Indicators
Over-voltage, over-current, and thermal shutdown with automatic restart
Front-panel green PWR LED, red FAULT LED
Over-voltage, over-current, and thermal shutdown with automatic restart
Front-panel green PWR LED, red FAULT LED
Mechanical & Environmental
Slot Requirement: One Series 90-70 rack slot, leftmost position
Dimensions: 335 mm × 32 mm × 145 mm (H×W×D)
Weight: 0.9 kg
Operating Temperature: 0 – 60 °C (derate 2 % per °C above 50 °C)
Relative Humidity: 5 – 95 % RH non-condensing
Slot Requirement: One Series 90-70 rack slot, leftmost position
Dimensions: 335 mm × 32 mm × 145 mm (H×W×D)
Weight: 0.9 kg
Operating Temperature: 0 – 60 °C (derate 2 % per °C above 50 °C)
Relative Humidity: 5 – 95 % RH non-condensing
Function Highlights
Hot insertion and removal under rack power for maintenance without system shutdown
Conformal-coated PCB for resistance to moisture, dust, and corrosive atmospheres
Parallel operation capability for N+1 redundancy using load-share circuitry
Front-panel reset push-button for controlled system restart
Hot insertion and removal under rack power for maintenance without system shutdown
Conformal-coated PCB for resistance to moisture, dust, and corrosive atmospheres
Parallel operation capability for N+1 redundancy using load-share circuitry
Front-panel reset push-button for controlled system restart
Typical Applications
Petrochemical offshore platform control systems
Steel caster secondary cooling water skids
Remote natural-gas compressor station SCADA
Water treatment plant filter backwash sequencing
Petrochemical offshore platform control systems
Steel caster secondary cooling water skids
Remote natural-gas compressor station SCADA
Water treatment plant filter backwash sequencing














There are no reviews yet.