Ripple & Noise: ≤50 mV pp
-
Hold-up Time: 10 ms minimum at full load
-
Inrush Current: 4 A peak for 100 ms max
-
Protection: Over-voltage, over-current, short-circuit, over-temperature
-
Indicators: LED for Power, P/S Fault, Over-temp, Overload
-
Wire Size: 14–18 AWG, 6 A rated terminals
-
Operating Temperature: 0 °C to +60 °C
-
Storage Temperature: –40 °C to +85 °C
-
Relative Humidity: 5 % to 95 % non-condensing
-
Mounting: DIN rail, single-slot RX3i backplane slot 0
-
Dimensions: 127 mm H × 50 mm W × 115 mm D
Functional Features
-
Compact 40 W footprint saves panel space while powering full-size RX3i racks
-
Triple isolated outputs eliminate ground loops and simplify wiring for mixed-signal systems
-
Hot-swap capability allows module exchange without powering down the rack
-
Front-panel On/Off switch with protective cover prevents accidental shutdown
-
Daisy-chain support enables two modules to share a single 24 Vdc feed without increasing capacity
Application Scenarios
-
Manufacturing Lines: Backplane power for modular RX3i PLCs controlling packaging, assembly, and conveying systems
-
Process Industries: Reliable 24 Vdc source for distributed I/O and valve banks in chemical and food & beverage plants
-
Energy & Utilities: Cabinet power for turbine controllers, substation automation, and solar inverter management
-
Water & Wastewater: Supply for SCADA RTUs, pump controllers, and chemical-dosing skids in treatment facilities














There are no reviews yet.