Mechanical & Environmental
Dimensions: 133 mm H × 69 mm W × 118 mm D
Weight: 0.18 kg
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 5 % – 95 % non-condensing
Shock: 15 g peak, 11 ms half-sine
Vibration: 2 g, 10 Hz – 500 Hz
Coating: Conformal-coated PCB for harsh environments
Enclosure: IP 20, UL 94 V-0 flammability rated
Dimensions: 133 mm H × 69 mm W × 118 mm D
Weight: 0.18 kg
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 5 % – 95 % non-condensing
Shock: 15 g peak, 11 ms half-sine
Vibration: 2 g, 10 Hz – 500 Hz
Coating: Conformal-coated PCB for harsh environments
Enclosure: IP 20, UL 94 V-0 flammability rated
Power Requirements
Backplane Current: 3.3 V @ 0.8 A, 5 V @ 0.2 A
Power Dissipation: 4 W max
Backplane Current: 3.3 V @ 0.8 A, 5 V @ 0.2 A
Power Dissipation: 4 W max
PROFINET Interface
Ethernet Ports: 2 × RJ-45, 10/100 Mbps, auto-negotiate, auto-MDIX
Cable Length: 100 m max per segment (Cat5e or better)
Isolation: 1 500 V RMS port-to-logic
Max Devices: 128
Max I/O per Device: 1 440 bytes input, 1 440 bytes output
Update Time: 1 ms – 512 ms, configurable per device
Supported Classes: PROFINET RT Class 1, RT Class 3 (IRT)
Ethernet Ports: 2 × RJ-45, 10/100 Mbps, auto-negotiate, auto-MDIX
Cable Length: 100 m max per segment (Cat5e or better)
Isolation: 1 500 V RMS port-to-logic
Max Devices: 128
Max I/O per Device: 1 440 bytes input, 1 440 bytes output
Update Time: 1 ms – 512 ms, configurable per device
Supported Classes: PROFINET RT Class 1, RT Class 3 (IRT)
Diagnostics & Indicators
-
RUN: Module health
-
NET: Network status
-
ERR: Fault indication
-
LINK/ACT & 10/100: Per-port activity and speed
Functional Features
-
PROFINET I/O Controller: Manages cyclic and acyclic data exchange, alarms, and diagnostics.
-
Dual Ethernet Ports: Enables ring, redundant star, or load-balanced topologies without external switches.
-
Conformal Coating: Protects against salt fog, sulfur, and condensing humidity.
-
Device Replacement: Automatic device replacement (ADR) simplifies maintenance.
-
Firmware Upgrade: In-system updates via Machine Edition or PROFINET firmware loader.
-
Transparent Redundancy: Works with redundant RX3i CPUs for fault-tolerant applications.
Application Scenarios
-
Automotive Manufacturing: Robot controllers, welding stations, and vision systems synchronized on PROFINET.
-
Packaging Lines: High-speed conveyors, servo drives, and barcode readers networked for rapid changeover.
-
Food & Beverage: Filling, labeling, and packaging machines requiring hygienic wash-down environments.
-
Electronics Assembly: SMT lines and test cells demanding deterministic data exchange.
-
Water & Wastewater: Distributed pump and valve skids communicating over PROFINET for real-time control.














There are no reviews yet.