Resolution
-
±10 V: 15.9 bits
-
0–10 V: 14.9 bits
-
0–20 mA: 15.9 bits
-
4–20 mA: 15.6 bits
Accuracy
-
±0.15 % of full scale @ 25 °C
-
±0.30 % of full scale @ 60 °C
Update Rate
-
8 ms per channel (HART disabled)
-
16 ms per channel (HART enabled)
Output Settling Time
-
Voltage: 2 ms (0–95 %)
-
Current: 23 ms without HART, 70 ms with HART
HART Communication
-
Version 5.0 on each channel
-
Two integrated HART modems (four channels per modem)
Data Format
-
IEEE 32-bit floating point
-
16-bit integer within 32-bit field
Isolation
-
2550 V DC field-to-backplane (1 s)
Load Capability
-
Voltage mode: 2 kΩ minimum
-
Current mode: 0–850 Ω maximum
Power Requirements
-
External supply: 19.2–30 V DC (24 V nominal)
-
Backplane: 380 mA max @ 3.3 V DC (HART enabled)
-
Module dissipation: 7.25 W max
Environmental Ratings
-
Operating temperature: 0 °C to 60 °C
-
Storage temperature: –40 °C to 85 °C
-
Relative humidity: 5 % to 95 %, non-condensing
-
Protection rating: IP20
Functional Highlights
-
Hot insertion and removal under power
-
Auto-calibration on power-up
-
Per-channel output clamping and alarm limits
-
Alarm latching and configurable bias
-
Removable terminal block with spring or screw connections
Applications
-
Process control systems driving HART-capable valve positioners, I/P converters and transmitters
-
Oil & gas, chemical and pharmaceutical batch and continuous processes
-
Water & wastewater treatment dosing and flow control loops
-
Factory automation requiring precise analog setpoints for drives and actuators
-
Retrofit and upgrade of legacy Series 90-30 and PLC-5 analog output modules














There are no reviews yet.